L2: Power Loss Ride Through; L3: Stall Prevention - YASKAWA CIPR-CR70A Series Technical Manual

Ac drive for cranes 200/400 v class: 0.4 to 110/315 kw
Table of Contents

Advertisement

No.
Name
(Hex.)
L1-03
Motor Thermistor
oH Alarm Select
(0482)
L1-04
Motor Thermistor
oH Fault Select
(0483)
L1-05
Motor Thermistor
Filter Time
(0484)
L1-08
oL1 Current Level
(1103)
L1-09
oL1 Current Level
for Motor 2
(1104)
L1-13
Motor Overload
Memory Selection Sets the function that keeps the current electronic thermal protector
(046D)

L2: Power Loss Ride Through

No.
Name
(Hex.)
L2-03
Minimum Baseblock
Time
(0487)
L2-05
Undervoltage
Detection Lvl (Uv1)
(0489)

L3: Stall Prevention

No.
Name
(Hex.)
L3-01
Stall Prevention
during Accel
(048F)
L3-02
Stall Prevent Level
during Accel
(0490)
L3-03
Stall Prevent Limit
during Accel
(0491)
YASKAWA ELECTRIC SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Selects the drive operation when the PTC input signal input into the
drive reaches the detection level of oH3 [Motor Overheat (PTC
Input)].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive operation when the PTC input signal to the drive is at
the oH4 [Motor Overheat Fault (PTC Input)] detection level.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the primary delay time constant for the PTC input signal
entered to the drive. This parameter prevents accidental motor
overheat faults.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the current value used as the reference for detecting the motor
overload state regarding the motor 1 electronic thermal protector.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the current value used as the reference for detecting the motor
overload state regarding the motor 2 electronic thermal protector.
V/f
CL-V/f
OLV
CLV
AOLV
value when the drive stops receiving power.
0 : Disabled
1 : Enabled
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum baseblock time when power is restored.
V/f
CL-V/f
OLV
CLV
AOLV
Determines the voltage at which a Uv1 [DC Bus Undervoltage] fault is
triggered. Usually it is not necessary to change this setting.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the method of the Stall Prevention During Acceleration function.
0 : Disabled
1 : Enabled
2 : Intelligent (Ignore Decel Ramp)
3 : Current Limit Method
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output current level used when the Stall Prevention function is
enabled during acceleration, as a percentage of the drive rated output
current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the lower limit for the stall prevention level during acceleration used
for constant output ranges as a percentage of the drive rated output current.
10 Parameter List
Default
Ref.
(Range)
3
278
(0 - 3)
1
279
(0 - 2)
0.20 s
707
(0.00 - 10.00 s)
0.0 A
707
(0.0 A or 10% to
150% of the drive
rated current)
0.0 A
707
(0.0 A or 10
to150% of the
drive rated current)
1
708
(0, 1)
Default
(Range)
Determined by o2-04
(0.1 - 5.0 s)
Determined by E1-01
(Determined by E1-
01)
Default
(Range)
1
(0 to 3)
Determined by L8-38
(0 - 150%)
50%
(0 - 100%)
475