H3: Analog Inputs - YASKAWA GA700 Technical Manual

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

10.10 H: Terminal Functions
Setting
Function
66
Comparator1
67
Comparator2
69
External Power
24V Supply
6A
Data Logger Error
90 to 93
DWEZ Digital
Outputs 1 to 4
A0 to A7
DWEZ Extended
Digital Output 1 to
8
100 to 1A7 Inverse Output of 0
to A7

H3: Analog Inputs

No.
Name
(Hex.)
H3-01
Terminal A1 Signal
Level Select
(0410)
H3-02
Terminal A1
Function Selection Sets a function for MFAI terminal A1.
(0434)
H3-03
Terminal A1 Gain
Setting
(0411)
RUN
H3-04
Terminal A1 Bias
Setting
(0412)
RUN
H3-05
Terminal A3 Signal
Level Select
(0413)
H3-06
Terminal A3
Function Selection Sets a function for MFAI terminal A3.
(0414)
H3-07
Terminal A3 Gain
Setting
(0415)
RUN
H3-08
Terminal A3 Bias
Setting
(0416)
RUN
560
V/f
CL-V/f
OLV
CLV
AOLV
The monitor value set with H2-20 [Comparator 1 Monitor Selection] is on while in range
of the time set with H2-24 [Comparator 1 On-Delay Time] and the values of H2-21
[Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit] are in range.
V/f
CL-V/f
OLV
CLV
AOLV
The monitor value set with H2-26 [Comparator 2 Monitor Selection] is on while in range
of the time set with H2-30 [Comparator 2 On-Delay Time] and the values of H2-27
[Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit] are in range.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when there is an external 24V power supply between terminals
PS-AC.
ON : An external 24V power supply supplies power.
OFF : An external 24V power supply does not supply power.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a LoG [Com Error / Abnormal SD card].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output. Refer to the DriveWorksEZ online manual for
more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the digital output for the DriveWorksEZ DO-A3 option card. Refer to the
DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Causes inverse output of the function for the selected MFDO. Uses the last two digits of
1xx to select which function to inversely output.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the analog signal input to MFAI terminal A1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the analog signal input to MFAI terminal A1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input signal level for MFAI terminal A3.
0 : 0-10V (LowLim=0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the analog signal input to MFAI terminal A3.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the analog signal input to MFAI terminal A3.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Ref.
909
910
910
910
911
911
911
Default
Ref.
(Range)
0
913
(0 - 3)
0
913
(0 - 32)
100.0%
913
(-999.9 - +999.9%)
0.0%
914
(-999.9 - +999.9%)
0
914
(0 - 3)
2
914
(0 - 32)
100.0%
915
(-999.9 - +999.9%)
0.0%
915
(-999.9 - +999.9%)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents