H3: Analog Inputs - YASKAWA CR700 Technical Manual

Hide thumbs Also See for CR700:
Table of Contents

Advertisement

Setting Value
Function
62
Modbus Reg 1 Status
Satisfied
63
Modbus Reg 2 Status
Satisfied
66
Comparator1
67
Comparator2
69
External Power 24V
Supply
6A
Data Logger Error
B1
DC Injection Braking at
Start
B2
DC Injection Braking at
Stop
B3
Motor 3 Selection
100 - 1FF
Inverse Output of 0 to
FF

H3: Analog Inputs

No.
Name
(Hex.)
H3-01
Terminal A1 Signal
Level Select
(0410)
H3-02
Terminal A1 Function
Selection
(0434)
H3-03
Terminal A1 Gain
Setting
(0411)
RUN
H3-04
Terminal A1 Bias
Setting
(0412)
RUN
H3-05
Terminal A3 Signal
Level Select
(0413)
H3-06
Terminal A3 Function
Selection
(0414)
H3-07
Terminal A3 Gain
Setting
(0415)
RUN
H3-08
Terminal A3 Bias
Setting
(0416)
RUN
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the bit specified by H2-08 [Modbus Register 1 Bit Select] for the MEMOBUS register
address set with H2-07 [Modbus Register 1 Address Select] activates.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the bit specified by H2-10 [Modbus Register 2 Bit Select] for the MEMOBUS register
address set with H2-09 [Modbus Register 2 Address Select] activates.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates if the monitor value set with H2-20 [Comparator 1 Monitor Selection] is in range of the
values of H2-21 [Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit] for the time set in H2-24
[Comparator 1 On-Delay Time].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates if the monitor value set with H2-26 [Comparator 2 Monitor Selection] is not in the range of
the values of H2-27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit] for the time set in H2-
30 [Comparator 2 On-Delay Time].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when there is an external 24V power supply between terminals PS-AC.
ON : The external 24V power supply is supplying power.
OFF : The external 24V power supply is not supplying power.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a LoG [Com Error / Abnormal SD card].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the motor is started and during DC Injection Braking.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the motor is stopped and during DC Injection Braking.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when you select motor 3.
ON : Motor 3 Selected
OFF : Motor 1 or Motor 2 Selected
V/f
CL-V/f
OLV
CLV
AOLV
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which
function to inversely output.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input signal level for MFAI terminal A1.
0 : 0-10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for MFAI terminal A1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the analog signal input to MFAI terminal A1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the analog signal input to MFAI terminal A1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input signal level for MFAI terminal A3.
0 : 0-10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for MFAI terminal A3.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the analog signal input to MFAI terminal A3.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the analog signal input to MFAI terminal A3.
10.10 H: Terminal Functions
Description
Ref.
722
722
722
722
723
723
723
723
723
216
226
723
Default
Ref.
(Range)
0
725
(0, 1)
0
726
(0 - FF)
100.0%
726
(-999.9 - +999.9%)
0.0%
726
(-999.9 - +999.9%)
0
726
(0, 1)
2
726
(0 - FF)
100.0%
727
(-999.9 - +999.9%)
0.0%
727
(-999.9 - +999.9%)
509