T4: Ez Tuning - YASKAWA GA700 Technical Manual

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

10.16 T: Motor Tuning
No.
Name
(Hex.)
T3-03
Motor Inertia
(0762)
T3-04
System Response
Frequency
(0763)

T4: EZ Tuning

No.
Name
(Hex.)
T4-01
EZ Tuning Mode
Selection
(3130)
T4-02
Motor Type
Selection
(3131)
T4-03
Motor Max
Revolutions
(3132)
T4-04
Motor Rated
Revolutions
(3133)
T4-05
Motor Rated
Frequency
(3134)
T4-06
Motor Rated
Voltage
(3135)
T4-07
Motor Rated
Current
(3136)
T4-08
Motor Rated
Capacity
(3137)
T4-09
Number of Poles
(3138)
598
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the inertia of the motor. This value uses the test signal response
to calculate the load inertia.
V/f
CL-V/f
OLV
CLV
AOLV
This parameter uses the load inertia value from the Inertia Tuning
process to automatically calculate and set C5-01 [ASR Proportional
Gain 1].
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the type of Auto-Tuning for EZOLV control.
0 : Motor Parameter Setting
1 : Line-to-Line Resistance
V/f
CL-V/f
OLV
CLV
AOLV
Sets the type of motor.
0 : Induction (IM)
1 : Permanent Magnet (PM)
2 : Synchronous Reluctance (SynRM)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the maximum motor revolutions (min
V/f
CL-V/f
OLV
CLV
AOLV
Sets rated rotation speed (min
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated frequency (Hz) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated voltage (V) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated current (A) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated capacity in 0.01 kW units.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of motor poles.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
-1
).
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
-1
) of the motor.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
Ref.
(Range)
Determined by o2-
1039
04, C6-01, and E5-
01
(0.0001 - 6.0000
kgm
2
)
10.0 Hz
1039
(0.1 - 50.0 Hz)
Default
Ref.
(Range)
0
1039
(0, 1)
0
1040
(0, 1, 2)
-
1040
((40 to 120 Hz) ×
60 × 2 / E9-08)
-
1040
((40 to 120 Hz) ×
60 × 2 / E9-08)
Determined by E9-
1040
01 and o2-04
(40.0 - 120.0 Hz)
200 V Class: 200.0
1040
V, 400 V Class:
400.0 V
(200 V Class: 0.0 -
255.0 V, 400 V
Class: 0.0 - 510.0
V)
Determined by o2-
1040
04 and C6-01
(10% to 200% of
the drive rated
current)
Determined by E9-
1041
10
(0.10 - 650.00 kW)
Determined by E9-
1041
01
(2 - 48)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents