A08555
Modbus TCP: commissioning error
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
CU_G130_DP, CU_G130_PN, CU_G150_DP, CU_G150_PN
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
A setting for the "Modbus TCP" protocol is incorrect.
Alarm value (r2124, interpret decimal):
1: Modbus simultaneously activated on the onboard interface (p2030) and CBE20 (p8835). CBE20 is not activated.
2: A drive object supported by Modbus is not available under p0978[0]. Modbus is not activated.
3: drive object SERVO is under p0978[0] - and FM bit LINMOT is set, Modbus is not activated.
See also: p0978 (List of drive objects), p2030 (Field bus int protocol selection), p8835 (CBE20 firmware selection)
Remedy:
For alarm value = 1:
Check the parameterization and if required, correct (p2030, p8835).
For alarm value = 2:
Appropriately resort the list of drive objects in p0978.
Modbus supports the following drive object: VECTOR
A08560
IE: Syntax error in configuration file
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
A syntax error has been detected in the ASCII configuration file for the Industrial Ethernet interface (X127). The
saved configuration file has not been loaded.
Note:
IE: Industrial Ethernet
Remedy:
- Check the interface configuration (p8900 and following), correct if necessary, and activate (p8905 = 1).
- Save the parameters for interface configuration (e.g. p8905 = 2)
or
- reconfigure the station via the "Edit Ethernet node" screen form (e.g. with STARTER commissioning software).
See also: p8905 (IE Interface configuration)
A08561
IE: Consistency error affecting adjustable parameters
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
A consistency error was detected when activating the configuration (p8905) for the Industrial Ethernet interface
(X127).
Alarm value (r2124, interpret decimal):
0: general consistency error
1: error in the IP configuration (IP address, subnet mask or standard gateway).
2: Error in the station names.
5: standard gateway is also set at the PROFINET onboard interface.
6: the station name is also set at the PROFINET onboard interface.
7: IP address is located in the same subnet as the IP address of the PROFINET onboard interface.
Note:
For alarm value = 0, 1, 2, 5, 7 the following applies: the configuration was not changed.
For alarm value = 6 the following applies: The new configuration was however activated.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
LOCAL
Propagation:
LOCAL
4 Faults and alarms
4.2 List of faults and alarms
1637