Note for fault value = 3:
If the value for the maximum possible absolute position (LU) is greater than 4294967296, then it is not possible to
make an adjustment due to an overflow.
For rotary encoders, the maximum possible absolute position (LU) is calculated as follows:
1. Motor encoder without position tracking
p2506 * p0433 * p2505 / (p0432 * p2504)
p2506 * p0433 * p2505 * p0421 / (p0432 * p2504) for multiturn encoders
2. Motor encoder with position tracking for measuring gear
p2506 * p0412 * p2505 / p2504
3. Motor encoder with position tracking for load gear
p2506 * p2721 * p0433 / p0432
4. Motor encoder with position tracking for load and measuring gear
p2506 * p2721
5. Direct encoder without position tracking
p2506 * p0433 / p0432
p2506 * p0433 * p0421 / p0432 for multiturn encoders
6. Direct encoder with position tracking for measuring gear
p2506 * p0412
F07494
LR: Drive Data Set changeover in operation
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A Drive Data Set changeover (DDS) with a change of the mechanical relationships (p2503 ... 2506), direction of
rotation (p1821) or the encoder assignment (p2502) was requested in operation.
Note:
DDS: Drive Data Set
Remedy:
To changeover the drive data set, initially, exit the "operation" mode.
A07495 (F, N)
LR: Reference function interrupted
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
An activated reference function (reference mark search or measuring probe evaluation) was interrupted.
Possible causes:
- an encoder fault has occurred (Gn_ZSW.15 = 1).
- position actual value was set during an activated reference function.
- simultaneously activate reference mark search and measuring probe evaluation (BI: p2508 and BI: p2509 = 1
signal).
- activated reference function (reference mark search or measuring probe evaluation) was deactivated (BI: p2508
and BI: p2509 = 0 signal).
- the input terminal for the measuring probe is not set.
Remedy:
- check the causes and resolve.
- reset the control (BI: p2508 and BI: p2509 = 0 signal) and activate the requested function.
- set the input terminal for the measuring probe (p0488, p0489 or p2517, p2518).
Reaction upon F:
OFF1 (OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
Reaction upon N:
NONE
Acknowl. upon N:
NONE
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1567