Temperature
sensor
+ temp
Hardware
X522.7
2 mA
smoothing 1 s
+
X522.8
-
KTY/PTC
- temp
<1> p4100
= 0: Evaluation disabled
= 1: PTC
= 2: KTY
<2> An alarm A35920 in the temperature evaluation of the TM31 is signaled to the next (downstream) vector control via the
special temperature value -300 °C.
<3> As a result of the wire breakage monitoring the maximum temperature that can be measured is limited to approx.
188.6 °C.
<4> A value > 250 °C de-activates the alarm or fault.
<5> For KTY p4103 = 0
Output from TempTimer (0).
For PTC p4103 = 0
delay time = 0s.
1
2
DO: TM31
Terminal Module 31 (TM31) - Temperature evaluation (KTY/PTC)
<1>
Sensortyp
p4100
Software
smoothing 0.5 s
<4>
A
KTY
D
PTC
R_Sensor
r4101
3
4
Alarm threshold
-48...251 °C
<1>
p4102[0] (100)
Sensortype
p4100
<3>
188.6 °C
R
KTY
2
T
PTC
1
0
-140 °C
-300
°C
5 K
1650 Ohm (PTC)
1
0
1
0
250 °C
-50 °C
Measured temperature
Alarm is present
-300 °C
5
6
fp_9576_51_eng.vsd
21.01.13 V04.07.00
p4099[0] (4000.00 μs)
A35211
"Alarm is present"
<4>
p4103
r4104.0
<5>
1
T
0
0
Fault threshold
1
F35207
-48...251 °C
"Fault is present"
p4102[1] (120)
r4104.1
<4>
1
only for KTY84
0
5 K
A35920
“Error temp_sensor ch 0“
<2>
0
TM31 temp act val
r4105
1
7
Function diagram
SINAMICS
8
- 9576 -