Error Handling - Siemens Synco 200 SEZ220 Documentation On Basics

Signal converter
Table of Contents

Advertisement

Wiring test
Fault status messages
Monitor input signals
Exercise caution when
changing identifiers!
24 / 46
Siemens
Building Technologies
Settings,
continued
... > COMMIS > TEST
Path:
Display
Name
X1
X1
...
...
X5
X5
Display.
Name
Xx --- / ooo
Sensor error Xx
5.4

Error handling

When quitting the COMMIS (Commissioning) menu, the unit checks which input
signals are connected:
• A sensor error message is displayed when one of these signals is subsequently
missing:
"Xx ---"
Signal missing (e.g. in the event of a cable break).
"Xx ooo"
Short-circuit (only applicable to passive signals).
• Outputs are set to predetermined values when the function blocks are unable to
run calculations due to a missing input signal (see function block section "Error
handling").
Changing the identifier for an inputs after the configuration for the other function
blocks is completed may cause certain functions for these blocks to become
inactive as otherwise they would have to operate on invalid units.
SEZ220 signal converter
Analog inputs X1...X5
Positions
Display the current measured value at
terminal X1, non-adjustable.
...
Display the current measured value at
terminal X5, non-adjustable.
Impact
Non-urgent fault (Simple Alarm, Prio Low,
without plant stop).
CE1P5146en
02.06.2008