T2: Pm Motor Auto-Tuning - YASKAWA GA700 Technical Manual

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

10.16 T: Motor Tuning
No.
Name
(Hex.)
T1-11
Motor Iron Loss
(070B)
T1-12
Test Mode
Selection
(0BDB)
T1-13
No-load voltage
(0BDC)

T2: PM Motor Auto-Tuning

No.
Name
(Hex.)
T2-01
PM Auto-Tuning
Selection
(0750)
T2-02
PM Motor Code
Selection
(0751)
T2-03
PM Motor Type
(0752)
T2-04
PM Motor Rated
Power
(0730)
T2-05
PM Motor Rated
Voltage
(0732)
T2-06
PM Motor Rated
Current
(0733)
T2-07
PM Motor Base
Frequency
(0753)
T2-08
Number of PM
Motor Poles
(0734)
596
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the iron loss for calculating the energy-saving coefficient.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to enable Test Mode after Stationary Auto-Tuning.
When you can operate the motor with a light load attached after
Stationary Auto-Tuning is complete, enable this parameter.
Note:
You must first set T1-10 [Motor Rated Slip Frequency] = 0 Hz to
enable this parameter.
0 : No
1 : Yes
V/f
CL-V/f
OLV
CLV
AOLV
Sets the no-load voltage of the motor. If no-load voltage is necessary
at rated speed for the motor test report, set the voltage in this
parameter. If the motor test report is not available, do not change
this parameter.
Note:
To get the same qualities as a Yaskawa 1000-series drive or
previous models, set this parameter = T1-03 [Motor Rated
Voltage] value.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the type of Auto-Tuning for PM motors.
0 : Manual Entry w/ Motor Data Sheet
1 : Stationary (Ld, Lq, R)
2 : Stationary (R Only)
3 : Z-Pulse Offset (Pole Position)
4 : Rotational (Ld, Lq, R, back-EMF)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the PM motor code for drives operating SMRA, SSR1, or
SST4-series Yaskawa PM motors.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the type of PM motor the drive will operate.
0 : IPM motor
1 : SPM motor
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated output power (kW) of a PM motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated voltage (V) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated current (A) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the base frequency (Hz) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of motor poles.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
Ref.
(Range)
Determined by E2-
1034
11 or E4-11
(0 - 65535 W)
0
1035
(0, 1)
90% of T1-03
1035
(200 V Class: 0.0 -
255.0 V, 400 V
Class: 0.0 - 510.0
V)
Default
Ref.
(Range)
0
1035
(Determined by
A1-02)
Determined by A1-
1036
02 and o2-04
(0000 - FFFF)
1
1036
(0, 1)
Determined by o2-
1036
04 and C6-01
(0.00 - 650.00 kW)
200 V Class: 200.0
1036
V, 400 V Class:
400.0 V
(200 V Class: 0.0 -
255.0 V, 400 V
Class: 0.0 - 510.0
V)
Determined by o2-
1036
04
(10% to 200% of
the drive rated
current)
87.5 Hz
1036
(0.0 - 590.0 Hz)
6
1037
(2 - 48)