E5: Pm Motor Settings; E9: Motor Setting - YASKAWA GA500 GA50U Series Programming Manual

Table of Contents

Advertisement

1.8 E: Motor Parameters

E5: PM Motor Settings

No.
Name
(Hex.)
E5-01
PM Motor Code Selection
(0329)
E5-02
PM Motor Rated Power
(032A)
E5-03
Motor Rated Current (FLA)
(032B)
E5-04
PM Motor Pole Count
(032C)
E5-05
PM Motor Resistance (ohms/
phase)
(032D)
E5-06
PM d-axis Inductance (mH/
phase)
(032E)
E5-07
PM q-axis Inductance (mH/
phase)
(032F)
E5-09
PM Back-EMF Vpeak (mV/
(rad/s))
(0331)
E5-24
PM Back-EMF L-L Vrms
(mV/rpm)
(0353)
E5-25
Polarity Estimation Timeout
(035E)
Expert

E9: Motor Setting

No.
Name
(Hex.)
E9-01
Motor Type Selection
(11E4)
E9-02
Maximum Speed
(11E5)
E9-03
Rated Speed
(11E6)
E9-04
Base Frequency
(11E7)
E9-05
Motor Rated Voltage
(11E8)
E9-06
Motor Rated Current (FLA)
(11E9)
E9-07
Motor Rated Power
(11EA)
44
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the motor code for Yaskawa PM motors. The drive uses the motor code to automatically set
some parameters to their correct settings.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the PM motor rated output in the units from o1-58 [Motor Power Unit Selection].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the PM motor rated current (FLA).
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the number of PM motor poles.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the resistance per phase of a PM motor. Set 50% of the line-to-line resistance.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the PM motor d-axis inductance.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the PM motor q-axis inductance.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the peak value of PM motor induced voltage.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the RMS value for PM motor line voltage.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function that switches polarity for initial polarity estimation. Usually it is not necessary to
change this setting.
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the type of motor.
0 : Induction (IM)
1 : Permanent Magnet (PM)
2 : Synchronous Reluctance (SynRM)
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the maximum speed of the motor.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the rated rotation speed of the motor.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the rated frequency of the motor.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the rated voltage of the motor.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the motor rated current in amps.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the motor rated output in the units from o1-58 [Motor Power Unit Selection].
Description
Description
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
Default
(Range)
FFFF
(0000 - FFFF)
Determined by o2-04, C6-01
(0.10 - 30.00 kW)
Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
4
(2 - 120)
0.100 Ω
(0.000 - 65.000 Ω)
1.00 mH
(0.00 - 300.00 mH)
1.00 mH
(0.00 - 600.00 mH)
0.0 mV/(rad/sec)
(0.0 - 2000.0 mV/(rad/s))
200 V Class:
100.0 mV/min
-1
400 V Class:
200.0 mV/min
-1
(0.0 - 6500.0 mV/min
-1
)
0
(0, 1)
Default
(Range)
0
(0 - 2)
Determined by E9-01
(40.0 - 120.0 Hz)
Determined by E9-01
(100 - 7200 min
-1
)
Determined by E9-01
(40.0 - 120.0 Hz)
200 V Class: 230.0 V,
400 V Class: 460.0 V
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
Determined by E9-01 and
o2-04
(10% to 200% of the drive
rated current)
Determined by E9-02 and
o2-04
(0.00 - 650.00 kW)

Advertisement