5.5 E: Motor Parameters
■
E1-08: Mid Point A Voltage
No.
Name
(Hex.)
E1-08
Mid Point A Voltage
(0307)
Note:
Default setting is determined by o2-04 [Drive Model Selection].
■
E1-09: Minimum Output Frequency
No.
Name
(Hex.)
E1-09
Minimum Output Frequency Sets the minimum output frequency for the V/f pattern.
(0308)
■
E1-10: Minimum Output Voltage
No.
Name
(Hex.)
E1-10
Minimum Output Voltage
(0309)
■
E1-11: Mid Point B Frequency
No.
Name
(Hex.)
E1-11
Mid Point B Frequency
(030A)
Expert
Note:
Set this parameter to 0.0 to disable the function.
■
E1-12: Mid Point B Voltage
No.
Name
(Hex.)
E1-12
Mid Point B Voltage
(030B)
Expert
Note:
Set this parameter to 0.0 to disable the function.
■
E1-13: Base Voltage
No.
Name
(Hex.)
E1-13
Base Voltage
(030C)
Expert
Note:
• After Auto-Tuning, the value of E1-13 = E1-05 [Maximum Output Voltage].
• When E1-13 = 0.0, use the value of E1-05 to control the voltage.
◆
E2: Motor Parameters
E2 parameters [Motor Parameters] set induction motor data. To switch drive operation from one motor to another
motor, configure the first motor (motor 1).
250
Sets a middle output voltage for the V/f pattern.
Sets the minimum output voltage for the V/f pattern.
Sets a middle output frequency for the V/f pattern.
Sets a middle point voltage for the V/f pattern.
Sets the base voltage for the V/f pattern.
Description
Description
Description
Description
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
(Range)
Determined by o2-04
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
Default
(Range)
1.5 Hz
(Determined by E1-04)
Default
(Range)
10.2 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
Default
(Range)
0.0 Hz
(0.0 - E1-04)
Default
(Range)
0.0 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
Default
(Range)
0.0 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)