D3: Jump Frequency; D4: Frequency Ref Up/Down & Hold; D6: Field Forcing; D7: Offset Frequency - YASKAWA CIPR-CR70A Series Technical Manual

Ac drive for cranes 200/400 v class: 0.4 to 110/315 kw
Table of Contents

Advertisement

10 Parameter List

d3: Jump Frequency

No.
Name
(Hex.)
d3-01
Jump Frequency 1
(0294)
d3-02
Jump Frequency 2
(0295)
d3-03
Jump Frequency 3
(0296)
d3-04
Jump Frequency
Width
(0297)
d4: Frequency Ref Up/Down & Hold
No.
Name
(Hex.)
d4-01
Freq Reference Hold
Selection
(0298)
d4-10
Up/Down Freq
Lower Limit Select
(02B6)

d6: Field Forcing

No.
Name
(Hex.)
d6-03
Field Forcing
Selection
(02A2)
d6-06
Field Forcing Limit
(02A5)

d7: Offset Frequency

No.
Name
(Hex.)
d7-01
Offset Frequency 1
(02B2)
RUN
d7-02
Offset Frequency 2
(02B3)
RUN
d7-03
Offset Frequency 3
(02B4)
RUN
440
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the median value of the frequency band that the drive will avoid.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the median value of the frequency band that the drive will avoid.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the median value of the frequency band that the drive will avoid.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the width of the frequency band that the drive will avoid.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets whether to save the frequency reference when the Stop command is
entered or the power supply is shut off.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the lower frequency limit for the Up/Down function.
0 : Greater of d2-02 or Analog
1 : d2-02
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the field forcing function.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the maximum level that Field Forcing can increase the excitation
current reference as a percentage of E2-03 [Motor No-Load Current].
Usually it is not necessary to change this setting.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the value to add to or subtract from the frequency reference when H1-
xx = 44 [MFDI Function Select = Add Offset Frequency 1 (d7-01)] as a
percentage of E1-04 [Maximum Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the value to add to or subtract from the frequency reference when H1-
xx = 45 [MFDI Function Select = Add Offset Frequency 2 (d7-02)] as a
percentage of E1-04 [Maximum Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the value to add to or subtract from the frequency reference when H1-
xx = 46 [MFDI Function Select = Add Offset Frequency 3 (d7-03)] as a
percentage of E1-04 [Maximum Output Frequency].
YASKAWA ELECTRIC SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
Default
(Range)
0.0 Hz
(Determined by A1-
02)
0.0 Hz
(Determined by A1-
02)
0.0 Hz
(Determined by A1-
02)
1.0 Hz
(Determined by A1-
02)
Default
(Range)
0
(0, 1)
0
(0, 1)
Default
(Range)
0
(0, 1)
400%
(100 - 400%)
Default
(Range)
0.0%
(-100.0 - +100.0%)
0.0%
(-100.0 - +100.0%)
0.0%
(-100.0 - +100.0%)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cr700

Table of Contents