D6: Field Forcing; D7: Offset Frequency - YASKAWA CR700 Technical Manual

Hide thumbs Also See for CR700:
Table of Contents

Advertisement

d6: Field Forcing

No.
Name
(Hex.)
d6-03
Field Forcing Selection
(02A2)
d6-06
Field Forcing Limit
(02A5)

d7: Offset Frequency

No.
Name
(Hex.)
d7-01
Offset Frequency 1
(02B2)
RUN
d7-02
Offset Frequency 2
(02B3)
RUN
d7-03
Offset Frequency 3
(02B4)
RUN
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the field forcing function.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the limit value for field forcing to increase the motor excitation current reference as
a percentage of E2-03 [Motor No-Load Current]. Usually it is not necessary to change
this setting.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the value to add to or subtract from the frequency reference when H1-xx = 44
[MFDI Function Select = Add Offset Frequency 1 (d7-01)] as a percentage of the
maximum output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the value to add to or subtract from the frequency reference when H1-xx = 45
[MFDI Function Select = Add Offset Frequency 2 (d7-01)] as a percentage of the
maximum output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the value to add to or subtract from the frequency reference when H1-xx = 46
[MFDI Function Select = Add Offset Frequency 3 (d7-01)] as a percentage of the
maximum output frequency.
10.7 d: Reference Settings
Default
Ref.
(Range)
0
631
(0, 1)
400%
632
(100 - 400%)
Default
Ref.
(Range)
0.0%
632
(-100.0 - +100.0%)
0.0%
632
(-100.0 - +100.0%)
0.0%
632
(-100.0 - +100.0%)
10
481