L4: Speed Detection - YASKAWA CR700 Technical Manual

Hide thumbs Also See for CR700:
Table of Contents

Advertisement

No.
Name
(Hex.)
L3-26
Additional DC Bus
Capacitors
(0455)
Expert
L3-27
Stall Prevention
Detection Time
(0456)
L3-35
Speed Agree Width for
Auto Decel
(0747)
Expert
L3-36
Current Suppression
Gain@Accel
(11D0)
L3-37
Current Limit P Gain @
Accel
(11D1)
Expert
L3-38
Current Limit I Time @
Accel
(11D2)
Expert
L3-39
Current Limit Filter
Time @Accel
(11D3)
L3-40
Current Limit S-Curve
@ Acc/Dec
(11D4)

L4: Speed Detection

No.
Name
(Hex.)
L4-01
Speed Agree Detection
Level
(0499)
L4-02
Speed Agree Detection
Width
(049A)
L4-03
Speed Agree Detection
Level(+/-)
(049B)
L4-04
Speed Agree Detection
Width(+/-)
(049C)
L4-05
Fref Loss Detection
Selection
(049D)
L4-06
Frequency Reference
@Loss of Ref
(04C2)
L4-07
Speed Agree Detection
Selection
(0470)
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the capacity for external main circuit capacitors. Usually it is not necessary to
change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a delay time between reaching the Stall Prevention level and starting the Stall
Prevention function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the width for speed agreement when L3-04 = 2 [Stall Prevention during Decel =
Intelligent (Ignore Decel Ramp)]. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain to suppress current and motor speed hunting during operation when L3-01
= 3 [Stall Prevention during Accel = Current Limit Method]. Usually it is not necessary
to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Suppresses current hunting during acceleration. Usually it is not necessary to change
this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Suppresses current hunting and overshooting that occurs when the drive stalls during
acceleration. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant to adjust the acceleration rate when L3-01 = 3 [Stall Prevention
during Accel = Current Limit Method]. Usually it is not necessary to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to enable and disable the best S-curve characteristic used for current-
limited acceleration.
0 : Disable
1 : Enabled
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level to detect speed agree or motor speed.
Sets the level to detect speed agree or motor speed when H2-01 to H2-05 = 2, 3, 4, 5
[MFDO Function Selection = Speed Agree 1, User-set Speed Agree 1, Frequency
Detection 1, Frequency Detection 2].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the width to detect speed agree or motor speed.
Sets the width to detect speed agree or motor speed when H2-01 to H2-05 = 2, 3, 4, 5
[MFDO Function Selection = Speed Agree 1, User-set Speed Agree 1, Frequency
Detection 1, Frequency Detection 2].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level to detect speed agree or motor speed.
Sets the level to detect speed agree or motor speed when H2-01 to H2-05 = 13, 14, 15,
16 [MFDO Function Selection = Speed Agree 2, User-set Speed Agree 2, Frequency
Detection 3, Frequency Detection 4].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the width to detect speed agree or motor speed.
Sets the width to detect speed agree or motor speed when H2-01 to H2-05 = 13, 14, 15,
16 [MFDO Function Selection = Speed Agree 2, User-set Speed Agree 2, Frequency
Detection 3, Frequency Detection 4].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the operation when the drive detects a loss of frequency reference.
0 : Stop
1 : Run at (L4-06 x Last Reference)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference as a percentage to continue drive operation after it detects a
frequency reference loss. The value is a percentage of the frequency reference before
the drive detected the loss.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the condition that activates speed detection.
0 : No Detection during Baseblock
1 : Detection Always Enabled
10.11 L: Protection Functions
Default
Ref.
(Range)
0 μF
(0 to 65000 μF)
50 ms
(0 - 5000 ms)
0.00 Hz
(0.00 - 1.00 Hz)
Determined by A1-02
(0.0 - 100.0)
5 ms
(0 - 100 ms)
10.0
(0.0 - 100.0)
100.0 ms
(1.0 - 1000.0 ms)
0
(0, 1)
Default
Ref.
(Range)
Determined by A1-02
(Determined by A1-02)
Determined by A1-02
(Determined by A1-02)
Determined by A1-02
(Determined by A1-02)
Determined by A1-02
(Determined by A1-02)
0
(0, 1)
80.0%
(0.0 - 100.0%)
0
(0, 1)
756
756
756
757
757
757
757
757
758
758
758
758
758
759
759
10
517

Advertisement