6.7.5 Clearing The Warning - YASKAWA SVC User Manual

Mp3000 series machine controller, motion control
Table of Contents

Advertisement

Changing the Setting of Common Parameter 24 (Multiturn
Limit)
The warning will be cleared when the control power supply to the MP3000 is turned OFF and
ON again.
1.
Use the Digital Operator to set common parameter 24 to the value of fixed parameter
No. 38.
2.
Turn the power supply to the slave SERVOPACK OFF and ON again.
A multiturn limit disagreement alarm (A.CC0) will occur in the slave SERVOPACK.
3.
Execute Fn013 (Multiturn Limit Setting) from the Digital Operator.
4.
Turn the power supply to the slave SERVOPACK OFF and ON again.
The A.CC0 alarm in the slave SERVOPACK will be cleared.
5.
Turn the control power supply to the slave SERVOPACK OFF and ON again.
This concludes the procedure.
6.7 Multiturn Limit Setting Disagreement Detection

6.7.5 Clearing the Warning

6
6-33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Svc32SvrSvr32

Table of Contents