10.4 Main Commands and Subcommands
10.4.4 Subcommand Details
Setting Parameters
Sub Command
Transmission Reference Output
Data 16
Transmission Reference Output
Data 31
Monitor Parameters
Subcommand Response Code IW0A
Subcommand Status
Transmission Reference Input
Data 16
Transmission Reference Input
Data 31
Read Fixed Parameters
Description
Reads out the set data of the specified fixed parameter.
Setting Parameters
Sub Command
Fixed Parameter Number
Monitor Parameters
Subcommand Response
Code
Subcommand Status
Fixed Parameter Monitor
10-34
Name
Register No.
OW0A
OW70
.
.
.
OW7F
Name
Register No.
IW0B
IW70
.
.
.
IW7F
Name
Register No.
OW0A
OW48
Name
Register No.
IW0A
IW0B
IL48
Setting Range
0 to 65535
0 to FFFFH
.
−
.
.
0 to FFFFH
Setting
Range
0 to 65535
08: Transmission Reference
Bit 0 (Command execution
flag)
Bit 3 (Command error com-
Bit
pleted status)
Bit 8 (Command execution
completed)
0 to FFFFH
Subcommand input data bytes 0 and 1
.
−
.
0 to FFFFH
.
−
0 to FFFFH
Setting Range
0 to 65535
0 to 63
Setting
Range
0 to 65535
09: Read Fixed Parameters
Bit 0 (Command execution
flag)
Bit 3 (Command error com-
pleted status)
Bit
Bit 8 (Command execution
completed)
−1 −
31
31
-2
to 2
Remarks
08: Transmission Reference
Subcommand output data bytes 0 and 1
−
−
Remarks
ON during
execution
Always OFF
Always OFF
Remarks
09: Read Fixed Parameters
Set the fixed parameter number.
Remarks
ON during execu-
tion
ON when an error
occurs during
command pro-
cessing.
OFF during exe-
cution, and ON
when execution
is completed.