Override
 Override
SVC
Set the percentage of the OL10 setting parameter (Speed Reference Setting) to output in
increments of 0.01%.
Register
Address
OW18
Override
Setting Precautions
• The Override parameter is always enabled. If you do not want to use this parameter, keep the
override set to 10,000.
• If the override is set to 0, the output speed is 0 and the motor will not operate.
Speed reference (OL10) × Override (OW18) = Output speed
• The override can be changed during execution of a speed reference. Acceleration or deceler-
ation occurs immediately according to the set value.
Speed
100%
75%
50%
10000
5000
Override set value
Position Reference Setting
 Position Reference Setting
Set the position reference.
Register
Address
OL1C Position Reference Setting
This parameter is used by the following motion commands.
1: POSING (Positioning).
2: EX_POSING (External Positioning).
4: INTERPOLATE (Interpolation).
6: LATCH (Interpolate with Latch Input).
Refer to the following chapter for details on these commands.
Chapter 4 Motion Control Program Commands and Instructions
Related Parameters
OW09 setting parameter, bit 5 (Position Reference Type)
Positioning Completion Width
 Positioning Completion Width
This parameter applies the set value of this parameter to the SERVOPACK parameter.
Refer to the following section for details.
3.5 Automatically Updated Parameters on page 3-86
Setting
Name
Range
0 to 32,767
7500
10000
SVC
Setting
Name
Range
Reference
units
SVC
3.4 Motion Parameter Details
3.4.2 Setting Parameter Details
Setting Unit
Default
0.01%
10,000
Time
SVR
Setting Unit
Default
−1
31
31
-2
to 2
Control mode
Position
Speed
Control mode
0
Position
3-49