10.5 Motion Parameter Details
10.5.5 Inverter Input Data Details
10.5.5 Inverter Input Data Details
The following table provides details on the data input to the A1000 and V1000 Inverters that
support MECHATROLINK-III.
Register No.
IW11
IW12
IW13
IW14
IW15
IW16
IW17
IW18
IW19
IW1A
IW1B
IW1C
10-60
Name
Output Frequency
Output Current
Motor Speed (Option)
Torque Reference (Option)
Encoder Count PG1
Frequency Reference (Option)
Analog Input A2
Main Bus Voltage (Option)
Alarm Code
Warning Code
Bit 0: Terminal 1
Status
Bit 1: Terminal 2
Status
Bit 2: Terminal 3
Status
Bit 3: Terminal 4
Status
Bit 4: Terminal 5
Status
Bit 5: Terminal 6
Status
Multi-Function
Bit 6: Terminal 7
Output Terminal
Status
Bit 7: Terminal 8
Status
Bit 8: Terminal 9
Status
Bit 9: Terminal
10 Status
Bit A: Terminal
11 Status
Bit B: Terminal
12 Status
Bits C to F
Analog Input A3
Description
The unit is determined by the setting of the O1-03
Inverter parameter.
Unit: 0.1 A or 0.01 A
The unit is determined by the setting of the O1-03
Inverter parameter. (Invalid in V/f with PG control
mode)
Unit: 0.1%
(Invalid in V/f with PG and V/f control mode)
Unit: pulse
(Invalid when an optional PG is not connected.)
The unit is determined by the setting of the O1-03
Inverter parameter.
Unit: 0.1%
Unit: 1 V
Inverter alarm code
Inverter warning code
0: OFF, 1: ON
0: OFF, 1: ON
0: OFF, 1: ON
0: OFF, 1: ON
0: OFF, 1: ON
0: OFF, 1: ON
0: OFF, 1: ON
0: OFF, 1: ON
0: OFF, 1: ON
0: OFF, 1: ON
0: OFF, 1: ON
0: OFF, 1: ON
Reserved
Unit: 0.1%
Continued on next page.