 SIZE: Read Data Size
 ADDRESS: First Read Address
 DATA: Data
 Execution and Operating Procedure
1.
Make sure that the following condition is met.
No.
Execution Condition
I/O command execution must be com-
1
pleted.
2.
Set the following parameters.
• MODE/DATA_TYPE (Mode/Data Type)
• SIZE (Read Data Size)
• ADDRESS (First Read Address)
Setting Precautions
Make any necessary changes to MODE/DATA_TYPE (Mode/Data Type), SIZE (Read Data Size), or
ADDRESS (First Read Address) before executing the Read Memory command or during the same
scan that the I/O Command register is set to 7. Do not change these settings during execution of the
Read Memory command.
3.
Set the I/O Command register to 7 to execute the Read Memory command.
 Confirming Completion of the Command
Use the following information to confirm that the command has been completed.
No.
1
I/O Command Response register = 7 (Read Memory)
2
Command Status bit 2 (CMDRDY) = 1
3
MODE/DATA_TYPE must be the same in the command and response.
4
SIZE must be the same in the command and response.
5
ADDRESS is the same in the command and response.
1. If the command is not completed within 5 seconds after it is executed, bit 0 in the Master Sta-
tus register changes to 1 (TIMEOUT).
2. When bit 0 (D_ALM) or bit 1 (D_WAR) in the Command Status register is 1, check the error
Important
details with the application and perform the stop processing. The system will not perform stop
processing.
11.3 MECHATROLINK-III I/O Module Settings
Command Status bit 2 (CMDRDY) = 1
Confirmation Method
11.3.4 I/O Command Details
Confirmation Method
11