10.2
Setup Procedure
This section describes how to set up Inverters using the MPE720.
10.2.1
Check Items before Setup
Confirm the following items before you set up an Inverter.
• For information on how to set Inverter constants and user constants, refer to the relevant
Inverter manual.
• The b1-01 Inverter parameter (Frequency Reference Selection 1) must be set to 3 (Option
Card or Option Unit).
• Inverter parameter b1-02 (Run Command Selection 1) must be set to 3 (Option Card or
Option Unit).
• The Inverter parameters shown in the following table must be correctly set.
Inverter
Parameter
No.
F6-20
MECHATROLINK Station Address
F6-21
MECHATROLINK Frame Size
MECHATROLINK Monitor Selec-
F6-23
tion (Code 0EH)
MECHATROLINK Monitor Selec-
F6-24
tion (Code 0FH)
Operation Selection at Watchdog
F6-25
Error (E5)
MECHATROLINK bUS Errors
F6-26
Detected
Name
20 to 3F hex: For A1000 software version S1018
or S1019, or V1000 software version S1022
03 to EF hex: For A1000 software version
S1020, or V1000 software version S1023
0: 64 bytes
1: 32 bytes
0 to FFFF hex
0 to FFFF hex
0: Decelerate to a stop (Decelerate to a stop
with the deceleration time in C1- 02)
1: Coast to stop
2: Emergency stop (Decelerate to a stop with
the emergency stop time in C1-09)
3: Continue operation
Set the number of bUS errors detected by SI-
ET3 or SI-ET3/V.
Setting range: 2 to 10
10.2 Setup Procedure
10.2.1 Check Items before Setup
Description
Default
Setting
21 hex
0
0 hex
0 hex
1
2
10