Y2: PID Sleep and Protection

Sleep Function
The Sleep Function uses the monitor data set in Y2-01 [Sleep Level Type] to know if the drive is necessary in the
system and turn off the drive.
This function helps to save the energy and prevent the deterioration on the motor.
*1
When Y2-01 = 5 [Output Frequency (non-PID)], the drive will ignore the Start Level set in Y1-04 [Sleep Wake-
up Level]. Set Y2-02 > 0 to enable the Sleep Function. The drive will enable the Sleep Function regardless of the
b5-01 setting or the status of the MFDI set for H1-xx = 19 [PID Disable].
Sleep Activation Level and Sleep Level
• Sleep Activation Level:
This level sets when the Sleep Function should start operation. You can use Y2-04 [Sleep Activation Level] or
Minimum Speed (the largest value from d2-02, Y1-06, and Y4-12) to set this level.
When the output frequency increases to more than the Sleep Activation Level, the Sleep Function will start to
monitor the system.
• Sleep Level:
This is the level that the drive uses to go to sleep (stop). You can use Y2-02 [Sleep Level] or Minimum Speed to set
this level.
Delta to Setpoint Entry for Sleep Wake-up Level
Delta to Setpoint Entry lets you set Y1-04 [Sleep Wake-up Level] relative to the current setpoint and set a PID setpoint
when PID is not active.
Parameter/Condition
b5-09 = 0 [PID Output Level Selection = Normal Output (Direct Acting)]
b5-09 = 1 [Reverse Output (Reverse Acting)]
Entry Mode
Absolute
Delta to Setpoint
412
Sets the maximum speed.
Y1-04
Y1-04
Table 5.66 Absolute Mode and Delta to Setpoint Mode
Keypad Display
Description
Delta Entry
-0.00 to -99.99
+0.00 to +99.99
The value set for Y1-04 represents the feedback level that will wake-up the drive. You can
set Y1-04 as an absolute value.
When the left-most digit changes to a Δ (delta), you can set a Sleep Wake-up Level relative
to the setpoint.
The effective Wake-up Level changes when b5-09 changes:
• b5-09 = 0: "Setpoint - Y1-04"
• b5-09 = 1: "Setpoint + Y1-04"
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
(Range)
0.0 Hz
(0.0 - 416.0)
Absolute Entry
0.00 to 99.99
0.00 to 99.99
Description