12.8 H: Terminal Functions

MFDO Setting Values

Selects the function configured to MFDO.
0: During Run
Setting Value
Function
0
During Run
ON : Drive is running
The drive is receiving a Run command or outputting voltage.
OFF : Drive is stopping
1: Zero Speed
Setting Value
Function
1
Zero Speed
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the reference.
A1-02 Setting
0
1
2
3
4
5
6
7
8
ON : Output frequency < value of E1-09 or b2-01.
914
V/f
CL-V/f
OLV
The terminal activates when you input a Run command and when the drive is outputting voltage.
Figure 12.89 Drive Running Time Chart
V/f
CL-V/f
OLV
The terminal activates when the output frequency < E1-09 [Minimum Output Frequency] or b2-01 [DC Injection/Zero
SpeedThreshold].
Control method selection
V/f Control
V/f Control with Encoder
Open Loop Vector
Closed Loop Vector
Advanced OpenLoop Vector Control
PM Open Loop Vector
PM Advanced Open Loop Vector
PM Closed Loop Vector Control
EZ Open Loop Vector Control
Figure 12.90 Zero Speed Time Chart
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Parameter Used as the Reference
E1-09
E1-09
b2-01
E1-09
E1-09
E1-09
E1-09
b2-01
E1-09