4 Faults and alarms
4.2 List of faults and alarms
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
ddccbbaa hex: aa = drive object category, bb = number limited, cc = actual number, dd = no significance
Remedy:
- power down the unit.
- suitably restrict the number of drive objects of the specified category by reducing the number of inserted
components.
- re-commission the unit.
F01152
CU: Invalid constellation of drive object types
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
It is not possible to simultaneously operate drive object types SERVO, VECTOR and HLA.
A maximum of 2 of these drive object types can be operated on a Control Unit.
Remedy:
- power down the unit.
- restrict the use of drive object types SERVO, VECTOR, HLA to a maximum of 2.
- re-commission the unit.
F01200
CU: Time slice management internal software error
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A time slice management error has occurred.
It is possible that the sampling times have been inadmissibly set.
Fault value (r0949, interpret hexadecimal):
998:
Too many time slices occupied by OA (e.g. DCC).
999:
Too many time slices occupied by the basic system. Too many different sampling times may have been set.
Additional values:
Only for internal Siemens troubleshooting.
Remedy:
- check the sampling time setting (p0112, p0115, p4099, p9500, p9511).
- contact the Hotline.
F01205
CU: Time slice overflow
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
Insufficient processing time is available for the existing topology.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- reduce the number of drives.
- increase the sampling times.
1300