Interconnection STW BOP (r0019)
Signal
Meaning
1 = On
STW BOP.0
0 = OFF (OFF1)
1 = No coast down
STW BOP.1
0 = Coast down (OFF2)
1 = No fast stop
STW BOP.2
0 = Fast stop (OFF3)
STW BOP.3
Reserved
STW BOP.4
Reserved
STW BOP.5
Reserved
STW BOP.6
Reserved
STW BOP.7
= Acknowledge fault
STW BOP.8
Reserved
STW BOP.9
Reserved
STW BOP.10
Reserved
STW BOP.11
Reserved
STW BOP.12
Reserved
STW BOP.13
1 = Motorized potentiometer, raise
STW BOP.14
1 = Motorized potentiometer, lower
STW BOP.15
Reserved
<1> The BICO interconnection represents an example that can be be changed by the user.
1
2
DO: CU_G, CU_S
Basic Operator Panel 20 (BOP20) - Control word interconnection
Interconnection
parameters
p0840[0] = r0019.0
p0844[0] = r0019.1
p0848[0] = r0019.2
p2102[0] = r0019.7
p1035[0] = r0019.13
p1036[0] = r0019.14
3
4
<1>
-
-
-
-
-
-
-
-
-
-
5
6
fp_9912_54_eng.vsd
03.07.13 V04.07.00
PROFIdrive sampling time
7
8
Function diagram
- 9912 -
S120/S150/G130/G150