Siemens SINAMICS G150 Manual page 1304

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
A01302
Error in the component trace
Message value:
%1
Message class:
General drive fault (19)
Drive object:
B_INF, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error has occurred in the component trace.
The message appears in the following cases:
- upload trace data (p7792 = 1).
- change factory setting (p7790, p7791) for missing property "component trace" (r0193.1 = 0).
Alarm value (r2124, interpret decimal):
1: The DRIVE-CLiQ component does not support the component trace (r0193.1 = 0).
101: Data from trace 1 cannot be read.
102: Data from trace 2 cannot be read.
103: Data from trace 3 cannot be read.
104: Data from trace 4 cannot be read.
105: Data from trace 5 cannot be read.
Remedy:
Re alarm value = 1:
Upgrade the firmware of the DRIVE-CLiQ component involved.
F01303
Component does not support the required function
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A function requested by the Control Unit is not supported by a DRIVE-CLiQ component.
Fault value (r0949, interpret decimal):
1: The component does not support the de-activation.
101: The Motor Module does not support an internal armature short-circuit.
102: The Motor Module does not support the de-activation.
201: The Sensor Module does not support actual value inversion (p0410.0 = 1) when using a Hall sensor (p0404.6 =
1) for the commutation.
202: The Sensor Module does not support parking/unparking.
203: The Sensor Module does not support the de-activation.
204: The firmware of this Terminal Module 15 (TM15) does not support the application TM15DI/DO.
205: The Sensor Module does not support the selected temperature evaluation (r0458).
206: The firmware of this Terminal Modules TM41/TM31/TM15 refers to an old firmware version. It is urgently
necessary to upgrade the firmware to ensure disturbance-free operation.
207: The power unit with this hardware version does not support operation with device supply voltages of less than
380 V.
208: The Sensor Module does not support de-selection of commutation with zero mark (via p0430.23).
211: The Sensor Module does not support single-track encoders (r0459.10).
212: The Sensor Module does not support LVDT sensors (p4677.0).
213: The Sensor Module does not support the characteristic type (p4662).
Remedy:
Upgrade the firmware of the DRIVE-CLiQ component involved.
For fault value = 205:
Check parameter p0600 and p0601 and if required, adapt interpretation.
For fault value = 207:
Replace the power unit or if required set the device supply voltage higher (p0210).
For fault value = 208:
Check parameter p0430.23 and reset if necessary.
1304
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents