• ET 200 (dec)
• NAMUR (r3113.x)
For the interfaces DP, ET 200, NAMUR, in some instances, the message classes are
combined.
Table 4-4
Message classes and coding of various diagnostic interfaces
Text of the message class (number according to PROFIdrive)
Cause and remedy.
Hardware/software errors (1)
A hardware or software malfunction was detected. Carry out a
POWER ON for the relevant component. If it occurs again, contact the
hotline.
Line fault (2)
A line supply fault has occurred (phase failure, voltage level ...).
Check the line supply and fuses. Check the supply voltage. Check the
wiring.
Supply voltage fault (3)
An electronics supply voltage fault (48 V, 24 V, 5 V ...) was detected.
Check the wiring. Check the voltage level.
DC-link overvoltage (4)
The DC-link voltage has assumed an inadmissibly high value. Check
the dimensioning of the system (line supply, reactor, voltages). Check
the infeed settings.
Power electronics fault (5)
An impermissible operating state of the power electronics was
detected (overcurrent, overtemperature, IGBT failure ...). Check
compliance with the permissible load cycles. Check the ambient
temperatures (fan).
Overtemperature of the electronic component (6)
The temperature in the component has exceeded the highest
permissible limit. Check the ambient temperature / control cabinet
ventilation.
Ground fault / inter-phase short-circuit detected (7)
A ground fault / inter-phase short-circuit was detected in the power
cables or in the motor windings. Check the power cables (connection).
Check the motor.
Motor overload (8)
The motor was operated outside the permissible limits (temperature,
current, torque ...). Check the load cycles and set limits. Check the
ambient temperature / motor cooling.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Specifies the "Error type" of the channel-related diagnostics for the
SIMATIC ET 200pro FC-2 device.
When the channel diagnostics are activated, the texts listed in the standard and the GSD
file of the ET 200pro can be displayed.
Specifies the bit number in parameter r3113.
4.1 Overview of faults and alarms
Diagnostics interface
PN
DS1
DP
(hex)
(dec)
(dec)
9000
0
16
9001
1
17
1
9002
2
2
2
3
9003
3
18
9004
4
19
9005
5
20
9006
6
21
9007
7
22
4 Faults and alarms
ET 200
NAMUR
(dec)
(r3113.x)
9
0
24
1
1
2
15
2
3
24
2
24
3
5
4
20
5
24
6
1273