4 Faults and alarms
4.2 List of faults and alarms
F01110
CU: More than one SINAMICS G on one Control Unit
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
More than one SINAMICS G type power unit is being operated from the Control Unit.
Fault value (r0949, interpret decimal):
Number of the second drive with a SINAMICS G type power unit.
Remedy:
Only one SINAMICS G drive type is permitted.
F01111
CU: Mixed operation of drive units illegal
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Illegal operation of various drive units on one Control Unit:
- SINAMICS S together with SINAMICS G
- SINAMICS S together with SINAMICS S Value or Combi
Fault value (r0949, interpret decimal):
Number of the first drive object with a different power unit type.
Remedy:
Only power units of one particular drive type may be operated with one Control Unit.
F01112
CU: Power unit not permissible
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The connected power unit cannot be used together with this Control Unit.
Fault value (r0949, interpret decimal):
1: Power unit is not supported (e.g. PM240).
2: DC/AC power unit connected to CU310 not permissible.
3: Power unit (S120M) not permitted for vector control.
Remedy:
Replace the power unit that is not permissible by a component that is permissible.
F01120 (A)
Terminal initialization has failed
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An internal software error occurred while the terminal functions were being initialized.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
- replace the Control Unit.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
1298
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A