Remedy:
Re fault value = 1, 5:
- reduce the computing time load of the drive unit (r9976[1] and r9976[5]) to under 100 %.
- check the sampling times and adjust if necessary (p0115, p0799, p4099).
- de-activate function modules.
- de-activate drive objects.
- remove drive objects from the target topology.
- note the DRIVE-CLiQ topology rules and if required, change the DRIVE-CLiQ topology.
When using the Drive Control Chart (DCC) or free function blocks (FBLOCKS), the following applies
- the computing time load of the individual run-time groups on a drive object can be read out in r21005 (DCC) or
r20005 (FBLOCKS).
- if necessary, the assignment of the run-time group (p21000, p20000) can be changed in order to increase the
sampling time (r21001, r20001).
- if necessary, reduce the number of cyclically calculated blocks (DCC) and/or function blocks (FBLOCKS).
F01055
CU: Internal error (SYNO of port and application not identical)
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
B_INF, TM150, VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
All applications that operate with slaves at one port must be derived from the same SYNO clock cycle.
The first application whose registration (log-on) connects a slave to a port defines the SYNO clock cycle that will be
used as basis for the port.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy:
Contact the Hotline.
F01056
CU: Internal error (clock cycle of parameter group already assigned differently)
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
B_INF, TM150, VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested parameter group (IREG, NREG, ...) is already being used in a different clock cycle.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy:
Contact the Hotline.
F01057
CU: Internal error (different DRIVE-CLiQ type for the slave)
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
B_INF, TM150, VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested DRIVE-CLiQ type (hps_ps, hps_enc, ...) has been specified differently for the same slave component.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy:
Contact the Hotline.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1293