Siemens SINAMICS G150 Manual page 1303

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

F01250
CU: CU-EEPROM incorrect read-only data
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE (OFF2)
Acknowledge:
POWER ON
Cause:
Error when reading the read-only data of the EEPROM in the Control Unit.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON.
- replace the Control Unit.
A01251
CU: CU-EEPROM incorrect read-write data
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
Error when reading the read-write data of the EEPROM in the Control Unit.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
For alarm value r2124 < 256, the following applies:
- carry out a POWER ON.
- replace the Control Unit.
For alarm value r2124 >= 256, the following applies:
- for the drive object with this alarm, clear the fault memory (p0952 = 0).
- as an alternative, clear the fault memory of all drive objects (p2147 = 1).
- replace the Control Unit.
F01255
CU: Option Board EEPROM read-only data error
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE (OFF2)
Acknowledge:
POWER ON
Cause:
Error when reading the read-only data of the EEPROM in the Option Board.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON.
- replace the Control Unit.
A01256
CU: Option Board EEPROM read-write data error
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
Error when reading the read-write data of the EEPROM in the Option Board.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON.
- replace the Control Unit.