Remedy:
Select the re-synchronization interval so that the synchronization deviation between the time master and drive
system lies within the tolerance window.
See also: r3108 (RTC last synchronization deviation)
A01100
CU: Memory card withdrawn
Message value:
-
Message class:
General drive fault (19)
Drive object:
B_INF, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory card (non-volatile memory) was withdrawn during operation.
Notice:
It is not permissible for the memory card to be withdrawn or inserted under voltage.
Remedy:
- power down the drive system.
- re-insert the memory card that was withdrawn - this card must match the drive system.
- power up the drive system again.
F01105 (A)
CU: Insufficient memory
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
OFF1
Acknowledge:
POWER ON
Cause:
Too many functions have been configured on this Control Unit (e.g. too many drives, function modules, data sets, OA
applications, blocks, etc).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- change the configuration on this Control Unit (e.g. fewer drives, function modules, data sets, OA applications,
blocks, etc).
- use an additional Control Unit.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01106
CU: Insufficient memory
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
B_INF, TM150, VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
There is not sufficient free memory space available.
Remedy:
Not necessary.
F01107
CU: Save to memory card unsuccessful
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A data save in the non-volatile memory was not able to be successfully carried out.
- non-volatile memory is defective.
- insufficient space in the non-volatile memory.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- try to save again.
- replace the memory card or Control Unit.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1297