SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SBR: Safe Brake Ramp (safe brake ramp monitoring)
SI: Safety Integrated
C01701
SI Motion P1 (CU): STOP B initiated
Message value:
-
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
VECTOR_G
Reaction:
NONE (OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive is stopped via a STOP B (braking along the OFF3 deceleration ramp).
As a result of this fault, after the time parameterized in p9556 has expired, or the speed threshold parameterized in
p9560 has been undershot, message C01700 "STOP A initiated" is output.
Possible causes:
- stop request from the second monitoring channel.
- subsequent response to the message C01714 "SI Motion CU: Safely-Limited Speed exceeded".
- subsequent response to the message C01711 "SI Motion CU: Defect in a monitoring channel".
- subsequent response to the message C01707 "SI Motion CU: tolerance for safe operating stop exceeded".
- subsequent response to the message C01715 "SI Motion CU: Safely-limited position exceeded".
- subsequent response to the message C01716 "SI Motion CU: tolerance for safe motion direction exceeded".
Remedy:
- remove the cause of the fault on the second monitoring channel.
- carry out a diagnostics routine for message C01714.
- carry out a diagnostics routine for message C01711.
- carry out a diagnostics routine for message C01707.
- carry out a diagnostics routine for message C01715.
- carry out a diagnostics routine for message C01716.
This message can be acknowledged without a POWER ON as follows:
- motion monitoring functions integrated in the drive: via Terminal Module 54F (TM54F) or PROFIsafe
- motion monitoring functions with SINUMERIK: via the machine control panel in acceptance test mode only
Note:
SI: Safety Integrated
C01706
SI Motion P1 (CU): SAM/SBR limit exceeded
Message value:
-
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Motion monitoring functions with encoder (p9506 = 0) or encoderless with set acceleration monitoring (SAM, p9506 =
3):
- after initiating STOP B (SS1) or STOP C (SS2), the speed has exceeded the selected tolerance.
Motion monitoring functions encoderless with set brake ramp monitoring (SBR p9506 = 1):
- after initiating STOP B (SS1) or SLS changeover to the lower speed stage, the speed has exceeded the selected
tolerance.
The drive is shut down by the message C01700 "SI Motion: STOP A initiated".
Remedy:
Check the braking behavior and, if necessary, adapt the parameterization of the parameter settings of the "SAM" or
the "SBR" function.
This message can be acknowledged without a POWER ON as follows:
- motion monitoring functions integrated in the drive: via Terminal Module 54F (TM54F) or PROFIsafe
- motion monitoring functions with SINUMERIK: via the machine control panel in acceptance test mode only
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1365