Siemens SINAMICS G150 Manual page 1318

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
A01383
Topology: Terminal Module incorrectly inserted
Message value:
Component: %1, to %2: %3, connection : %4
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a Terminal Module in the actual topology that has been incorrectly inserted
with respect to the target technology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterization in the commissioning software (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
A01384
Topology: DRIVE-CLiQ Hub Module incorrectly inserted
Message value:
Component: %1, to %2: %3, connection : %4
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a DRIVE-CLiQ Hub Module in the actual topology that has been incorrectly
inserted with respect to the target topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterization in the commissioning software (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
1318
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A