4 Faults and alarms
4.2 List of faults and alarms
Remedy:
- check the safety-relevant parameters and if required, correct.
- execute the function "Copy RAM to ROM".
- perform a POWER ON if safety parameters requiring a POWER ON have been modified.
- carry out an acceptance test.
F01681
SI Motion P1 (CU): Incorrect parameter value
Message value:
Parameter: %1, supplementary information: %2
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The parameter cannot be parameterized with this value.
Note:
This message does not result in a safety stop response.
Fault value (r0949, interpret decimal):
yyyyxxxx dec: yyyy = supplementary information, xxxx = parameter
yyyy = 0:
No information available.
xxxx = 9500 and yyyy = 1:
Parameter p9500 is not equal to p9300 or not an integer multiple of the sampling time of the current controller
(p0115[0]).
xxxx = 9501:
It is not permissible to enable the function "n < nx hysteresis and filtering" (p9501.16) in conjunction with the function
"Extended functions without selection" (p9601.5).
xxxx = 9501 and yyyy = 8:
Referencing via SCC (p9501.27 = 1) is enabled without enabling an absolute motion monitoring function (p9501.1 or
p9501.2).
xxxx = 9501 and yyyy = 10:
Referencing via SCC (p9501.27 = 1) and epos (r108.4=1) are simultaneously enabled.
xxxx = 9505:
When SLP is active (p9501.1 = 1), the modulo function is activated and this is not permitted (p9505 not equal to 0).
xxxx = 9506 and yyyy = 1:
Parameter p9506 is not equal to p9306.
xxxx = 9511 and yyyy = 1:
Parameter p9511 is not equal to p9311.
xxxx = 9511 and yyyy = 2:
On a Double Motor Module, between the drive objects, no different values in p9511 and p0115[0] is permitted.
xxxx = 9522:
The gear stage was set too high.
xxxx = 9534 or 9535:
The limit values of SLP have been set too high (absolute values).
xxxx = 9544:
For linear axes, the maximum value is limited to 1 mm.
xxxx = 9547:
Parameter p9547 has been set too low.
xxxx = 9573:
"Referencing via safety control channel" was requested (p9573=263), without enabling the function "Referencing via
SCC" (p9501.27=0).
xxxx = 9585:
For Safety without encoder and synchronous motor, p9585 must be set to 4.
xxxx = 9601 and yyyy = 1:
If motion monitoring functions integrated in the drive (p9601.2 = 1) and extended functions without selection (p9601.5
= 1) are enabled, then PROFIsafe (p9601.3 = 1) or onboard F-DI (p9601.4 = 1) is not possible.
xxxx = 9601 and yyyy = 2:
Extended functions without selection (p9601.5 =1) are enabled without enabling motion monitoring functions
integrated in the drive (p9601.2).
1354
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A