4 Faults and alarms
4.2 List of faults and alarms
For fault value = 16:
- inhibit the internal voltage protection (p1231).
For fault value = 20:
- correct setting in p9601.
For fault value = 22:
- use a Power Module that supports the Safety Integrated functions.
Note:
CU: Control Unit
ESR: Extended Stop and Retract
MM: Motor Module
SBA: Safe Brake Adapter
SBC: Safe Brake Control
SI: Safety Integrated
SS1: Safe Stop 1 (corresponds to Stop Category 1 acc. to EN60204)
STO: Safe Torque Off / SH: Safe standstill
See also: p9501 (SI Motion enable safety functions (Control Unit)), p9601 (SI enable functions integrated in the drive
(Control Unit)), p9620 (SI signal source for STO (SH)/SBC/SS1 (Control Unit)), p9761 (SI password input), p9801 (SI
enable functions integrated in the drive (Motor Module))
F01660
SI P1 (CU): Safety-related functions not supported
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The Motor Module/Hydraulic Module does not support the safety-related functions (e.g. the Motor Module/Hydraulic
Module version is not the correct one). Safety Integrated cannot be commissioned.
Note:
This fault does not result in a safety stop response.
Remedy:
- use a Motor Module/Hydraulic Module that supports the safety-related functions.
- upgrade the Motor Module/Hydraulic Module software.
Note:
CU: Control Unit
SI: Safety Integrated
F01661
SI P1 (CU): Simulation of the safety inputs active
Message value:
Fault cause: %1 bin
Message class:
General drive fault (19)
Drive object:
VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The simulation of the digital inputs of the Control Unit (p0795) is active.
It is not permissible that safety inputs are simulated.
Fault value (r0949, interpret binary):
The displayed bits indicate which digital inputs must not be simulated.
Remedy:
- Deactivate the simulation of the digital inputs of the Control Unit for the safety inputs (p0795).
- acknowledge fault.
F01663
SI P1 (CU): Copying the SI parameters rejected
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
In p9700, the value 87 or 208 is saved or was entered offline.
1348
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A