Assigning An Ip Address - Siemens Sinamics S120 Comissioning Manual

With startdrive
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Commissioning
4.4 Establishing an online connection to the drive
If the communication parameters are at their factory settings (IP address 0.0.0.0 and no
device name), then the default device names of the TIA Portal ("Node" in this case) and
the MAC address are displayed.
If you want to go online on the device, you must assign an IP address and a device
name.
4. Select the drive, and if necessary assign an IP address and device name, see also
"Assigning an IP address (Page 96)" and "Assigning PROFINET device names
(Page 98)".
Figure 4-34
The drive is displayed with the device name (in this case, drive_1) and the IP address.
If you cannot assign an IP address and device name, you may have to check the IP
address of your PG/PC. This must also lie in the same address range as the address of
the drive, see also "Setting the PG/ PC interface (Page 100)".
Result
You have found the device in the PROFINET subnet and assigned an IP address and a
device name.
Now establish an online connection.
4.4.3.3

Assigning an IP address

Adapting the IP address in the drive
Before you can go online on a drive via PROFINET, you must assign the PROFINET
interface of the drive a suitable IP address.
● When supplied, the PROFINET interface of the drive has no IP address.
● If a cyclic connection already exists from SINAMICS to the controller, it is no longer
possible to assign an IP address.
The PROFINET interface has already been assigned an IP address and subnet mask in the
project:
● IP address: 192.168.0.1
● Subnet mask: 255.255.255.0
The IP address and subnet mask lie in the subnet of an S71500 control, which simplifies
networking the control system and drive.
96
PROFINET with IP address
Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
Commissioning with Startdrive