Motor without DRIVE-CLiQ: Once the Control Unit has been switched on for the first time or if the factory settings
have been defined accordingly, the motor type is pre-configured as induction motor (p0300 = 1).
With p0300 = 10000, for a motor with DRIVE-CLiQ, the motor parameters are automatically downloaded, with p0300
= 10001, the motor parameters of a second data set (if available).
If a motor type has not been selected (p0300 = 0), then the drive commissioning routine cannot be exited.
A motor type with a value above p0300 >= 100 describes motors for which a motor parameter list exists.
Motor types with a value below p0300 < 100 correspond to the selection of a third-party motor. When appropriately
selected, this means that the motor parameters are pre-assigned the settings for a third-party motor.
This also applies for parameters for a motor with DRIVE-CLiQ. In this case p0300 can only be set to p0300 = 10000
or 10001 (read motor parameters) or to the corresponding non-Siemens motor (first digit of the motor code number)
in order to be able to cancel the write protection.
p0301[0...n]
Motor code number selection / Mot code No. sel
Access level: 2
Can be changed: C(1, 3)
Unit group: -
Min
0
Description:
The parameter is used to select a motor from a motor parameter list.
When changing the code number (with the exception to the value 0), all of the motor parameters are pre-assigned
from the internally available parameter lists.
Dependency:
Code numbers can only be selected for motor types that correspond to the motor type selected in p0300.
Refer to: p0300
Note:
The motor code number can only be changed if the matching catalog motor was first selected in p0300.
When selecting a catalog motor (p0300 >= 100), drive commissioning can only be exited if a code number is
selected.
If a change is made to a non-catalog motor, then the motor code number should be reset (p0301 = 0).
r0302[0...n]
Motor code number of motor with DRIVE-CLiQ / Mot code mot w/ DQ
Access level: 2
Can be changed: -
Unit group: -
Min
-
Description:
Displays the motor code number from the saved motor data from a motor with DRIVE-CLiQ.
Note:
Drive commissioning can only be exited if the code number that was downloaded (r0302) matches the stored code
number (p0301). If the numbers differ, then the motor data set should be re-loaded using p0300 = 10000.
The motor data are always expected from the first encoder that is assigned to the drive data sets (refer to p0187 =
encoder 1) data set number.
The value is not updated cyclically but only on specific events (e.g. update DRIVE-CLiQ device).
r0302 = 0: No motor with DRIVE-CLiQ found
p0304[0...n]
Rated motor voltage / Mot U_rated
Access level: 1
Can be changed: C(1, 3)
Unit group: -
Min
0 [Vrms]
Description:
Sets the rated motor voltage (rating plate).
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
Once the Control Unit has booted for the first time or if the factory settings have been restored, the parameter is pre-
assigned to match the power unit.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: -
Scaling: -
Unit selection: -
Max
65535
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
20000 [Vrms]
2 Parameters
2.2 List of parameters
Data type: Unsigned16
Dyn. index: MDS
Func. diagram: -
Factory setting
0
Data type: Unsigned16
Dyn. index: MDS
Func. diagram: -
Factory setting
-
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 6301, 6724
Factory setting
0 [Vrms]