p2024[0...2]
Fieldbus interface times / Fieldbus times
CU250S_V
Access level: 3
Can be changed: U, T
Unit group: -
Min
0 [ms]
Description:
Sets the time values for the fieldbus interface.
For Modbus the following applies:
p2024[0, 1]: Not relevant.
p2024[2]: Telegram pause time (pause time between two telegrams).
Index:
[0] = Max. processing time
[1] = Character delay time
[2] = Telegram pause time
Dependency:
Refer to: p2020, p2030
Note:
For p2024[2] (Modbus):
If the field bus baud rate is changed (p2020), the default time setting is restored.
The default setting corresponds to a time of 3.5 characters (dependent on the baud rate that has been set).
r2029[0...7]
Field bus interface error statistics / Field bus error
CU250S_V
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the receive errors on the field bus interface (RS485).
Index:
[0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
p2030
Field bus interface protocol selection / Field bus protocol
CU250S_V
Access level: 1
Can be changed: T
Unit group: -
Min
0
Description:
Sets the communication protocol for the field bus interface.
Value:
0:
1:
2:
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
No protocol
USS
Modbus RTU
Calculated: -
Scaling: -
Unit selection: -
Max
10000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
2
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 9310
Factory setting
[0] 1000 [ms]
[1] 0 [ms]
[2] 0 [ms]
Data type: Unsigned32
Dyn. index: -
Func. diagram: 9310
Factory setting
-
Data type: Integer16
Dyn. index: -
Func. diagram: 9310
Factory setting
0
317