2 Parameters
2.2 List of parameters
Dependency:
The following applies: p2182 < p2183 < p2184
Refer to: p2182, p2183, p2189, p2190
Refer to: A07926
Note:
In order that the load monitoring can reliably respond, the speed threshold p2184 should always be set higher than
the maximum motor speed to be monitored.
p2185[0...n]
Load monitoring torque threshold 1 upper / M_thresh 1 upper
CU250S_V (Ext msg)
Access level: 3
CU250S_V_CAN (Ext
Can be changed: U, T
msg)
Unit group: 7_1
CU250S_V_DP (Ext
Min
msg)
0.00 [Nm]
CU250S_V_PN (Ext
msg)
Description:
Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency:
The following applies: p2185 > p2186
Refer to: p2182, p2186
Refer to: A07926
Note:
The upper envelope curve is defined by p2185, p2187 and p2189.
p2186[0...n]
Load monitoring torque threshold 1 lower / M_thresh 1 lower
CU250S_V (Ext msg)
Access level: 3
CU250S_V_CAN (Ext
Can be changed: U, T
msg)
Unit group: 7_1
CU250S_V_DP (Ext
Min
msg)
0.00 [Nm]
CU250S_V_PN (Ext
msg)
Description:
Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency:
The following applies: p2186 < p2185
Refer to: p2182, p2185
Refer to: A07926
Note:
The lower envelope curve is defined by p2186, p2188 and p2190.
p2187[0...n]
Load monitoring torque threshold 2 upper / M_thresh 2 upper
CU250S_V (Ext msg)
Access level: 3
CU250S_V_CAN (Ext
Can be changed: U, T
msg)
Unit group: 7_1
CU250S_V_DP (Ext
Min
msg)
0.00 [Nm]
CU250S_V_PN (Ext
msg)
Description:
Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency:
The following applies: p2187 > p2188
Refer to: p2183, p2188
Refer to: A07926
Note:
The upper envelope curve is defined by p2185, p2187 and p2189.
358
Calculated: -
Scaling: -
Unit selection: p0505
Max
20000000.00 [Nm]
Calculated: -
Scaling: -
Unit selection: p0505
Max
20000000.00 [Nm]
Calculated: -
Scaling: -
Unit selection: p0505
Max
20000000.00 [Nm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8013
Factory setting
10000000.00 [Nm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8013
Factory setting
0.00 [Nm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8013
Factory setting
10000000.00 [Nm]
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890