p1562[0...n]
Moment of inertia estimator change time load / J_est t load
Access level: 3
Can be changed: U, T
Unit group: -
Min
5.00 [ms]
Description:
Sets the change time for the load torque for the moment of inertia estimator.
Lower values mean that faster changes are possible.
For a higher value, this estimated value is smoothed more significantly.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1400, p1560, p1561
p1563[0...n]
CO: Mom. of inertia estimator load torque direction of rotation pos. / J_est M pos
Access level: 3
Can be changed: U, T
Unit group: -
Min
-340.28235E36 [Nm]
Description:
Display and connector output for the monitored load torque in the positive direction of rotation.
The moment of inertia estimator estimates the load torque drawn while the speed is constant.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1400, p1560, p1561
p1564[0...n]
CO: Mom. of inertia estimator load torque direction of rotation neg. / J_est M neg
Access level: 3
Can be changed: U, T
Unit group: -
Min
-340.28235E36 [Nm]
Description:
Display and connector output for the monitored load torque in the negative direction of rotation.
The moment of inertia estimator estimates the load torque drawn while the speed is constant.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1400, p1560, p1561
p1570[0...n]
CO: Flux setpoint / Flex setp
Access level: 3
Can be changed: U, T
Unit group: -
Min
50.0 [%]
Description:
Sets the flux setpoint referred to rated motor flux.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
For p1570 > 100%, the flux setpoint increases as a function of the load from 100% (no-load operation) to the setting
in p1570 (above rated motor torque), if p1580 > 0% has been set.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
5000.00 [ms]
Calculated: -
Scaling: p2003
Unit selection: -
Max
340.28235E36 [Nm]
Calculated: -
Scaling: p2003
Unit selection: -
Max
340.28235E36 [Nm]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.0 [%]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
10.00 [ms]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
0.00 [Nm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
0.00 [Nm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6722
Factory setting
100.0 [%]