2 Parameters
2.2 List of parameters
p1744[0...n]
Motor model speed threshold stall detection / MotMod n_thr stall
Access level: 4
Can be changed: U, T
Unit group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed threshold value to detect a stalled motor.
If the adaptation controller output exceeds the parameterized speed difference, then in status word r1408.11 is set =
1.
Dependency:
If a stalled drive is detected (r1408.11 = 1), fault F07902 is output after the delay time set in p2178.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p2178
Note:
Speed monitoring is only effective in operation with a speed encoder (refer to p1300).
Stalling is also identified if steps/jumps occur in the speed signal, which exceed the value in p0492.
p1745[0...n]
Motor model error threshold stall detection / MotMod ThreshStall
Access level: 3
Can be changed: U, T
Unit group: -
Min
0.0 [%]
Description:
Sets the fault threshold in order to detect a motor that has stalled.
If the error signal (r1746) exceeds the parameterized error threshold, then status signal r1408.12 is set to 1.
Dependency:
If a stalled drive is detected (r1408.12 = 1), fault F07902 is output after the delay time set in p2178.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p2178
Note:
Monitoring is only effective in the low-speed range (below p1755 * (100% - p1756)).
r1746
Motor model error signal stall detection / MotMod sig stall
Access level: 3
Can be changed: -
Unit group: -
Min
- [%]
Description:
Signal to initiate stall detection
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note:
The signal is not calculated while magnetizing and only in the low speed range (below p1755 * (100 % - p1756)).
p1749[0...n]
Motor model increase changeover speed encoderless operation / Incr n_chng no enc
Access level: 4
Can be changed: U, T
Unit group: -
Min
0.0 [%]
Description:
Minimum operating frequency for rugged operation.
If the minimum value is greater than the lower changeover limit parameterized with p1755 * (1 - 2 * p1756), then the
difference is displayed using p1749 * p1755. The parameter value cannot be changed.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1752, p1755, p1756
282
Calculated: p0340 = 1,3
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
Calculated: p0340 = 1,3
Scaling: -
Unit selection: -
Max
1000.0 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
- [%]
Calculated: p0340 = 1,3
Scaling: -
Unit selection: -
Max
99.0 [%]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
100.00 [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
5.0 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [%]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
50.0 [%]
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890