Siemens SINAMICS G120 List Manual page 45

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

r0074
CO: Modulat_depth / Mod_depth
Access level: 4
Can be changed: -
Unit group: -
Min
- [%]
Description:
Display and connector output for the actual modulation depth.
Dependency:
Refer to: r0028
Note:
For space vector modulation, 100% corresponds to the maximum output voltage without overcontrol.
Values above 100 % indicate an overcontrol condition - values below 100% have no overcontrol.
The phase voltage (phase-to-phase, rms) is calculated as follows:(r0074 x r0070) / (sqrt(2) x 100 %).
The modulation depth is available smoothed (r0028) and unsmoothed (r0074).
r0075
CO: Current setpoint field-generating / Id_set
Access level: 3
Can be changed: -
Unit group: 6_2
Min
- [Arms]
Description:
Display and connector output for the field-generating current setpoint (Id_set).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note:
This value is irrelevant for the U/f control mode.
r0076
CO: Current actual value field-generating / Id_act
Access level: 3
Can be changed: -
Unit group: 6_2
Min
- [Arms]
Description:
Display and connector output for the field-generating current actual value (Id_act).
Dependency:
Refer to: r0029
Note:
This value is irrelevant for the U/f control mode.
The field-generating current actual value is available smoothed (r0029) and unsmoothed (r0076).
r0077
CO: Current setpoint torque-generating / Iq_set
Access level: 3
Can be changed: -
Unit group: 6_2
Min
- [Arms]
Description:
Display and connector output for the torque-generating current setpoint.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note:
This value is irrelevant for the U/f control mode.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
- [%]
Calculated: -
Scaling: p2002
Unit selection: p0505
Max
- [Arms]
Calculated: -
Scaling: p2002
Unit selection: p0505
Max
- [Arms]
Calculated: -
Scaling: p2002
Unit selection: p0505
Max
- [Arms]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 5730, 6730, 6731,
6799, 8940, 8950
Factory setting
- [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6700, 6714, 6725
Factory setting
- [Arms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 5700, 5714, 5730,
6700, 6714, 6799
Factory setting
- [Arms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6700, 6710
Factory setting
- [Arms]
45