2 Parameters
2.2 List of parameters
p2116[0...n]
BI: External alarm 2 / External alarm 2
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for external alarm 2.
Dependency:
Refer to: A07851
Note:
An external alarm is triggered with a 1/0 signal.
p2117[0...n]
BI: External alarm 3 / External alarm 3
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for external alarm 3.
Dependency:
Refer to: A07852
Note:
An external alarm is triggered with a 1/0 signal.
p2118[0...19]
Change message type message number / Chng type msg_no
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Selects faults or alarms for which the message type should be changed.
Dependency:
Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2119
Note:
Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
p2119[0...19]
Change message type type / Change type type
Access level: 3
Can be changed: U, T
Unit group: -
Min
1
Description:
Sets the message type for the selected fault or alarm.
Value:
1:
2:
3:
Dependency:
Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2118
Note:
Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
The message type can only be changed for messages with the appropriate identification (exception, value = 0).
Example:
F12345(A) --> Fault F12345 can be changed to alarm A12345.
In this case, the message number that may be possibly entered in p2100[0...19] and p2126[0...19] is automatically
removed.
342
Fault (F)
Alarm (A)
No message (N)
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
65535
Calculated: -
Scaling: -
Unit selection: -
Max
3
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2546
Factory setting
1
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2546
Factory setting
1
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8050, 8075
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: 8050, 8075
Factory setting
1
SINAMICS G120 CU250S-2 Control Units