Siemens SINAMICS G120 List Manual page 604

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

2 Parameters
2.2 List of parameters
Note:
The delay time must be set to a value greater than the debounce time (p10017).
Regardless of p10001, the forced checking procedure will pause for at least two safety monitoring clock cycles
between each stage of the test.
The test stop is only performed if the safety output is being used (p10142).
p10102
SI Motion F-DI changeover discrepancy time (processor 2) / SI Mtn F-DI t P2
Access level: 3
Can be changed: C(95)
Unit group: -
Min
1.00 [ms]
Description:
Sets the discrepancy time for digital inputs.
The signal states at the two associated digital inputs (F-DI) must assume the same state within this discrepancy time.
Dependency:
Refer to: p10002
Note:
F-DI: Fail-safe Digital Input
p10106
SI Motion acknowledgment internal event F-DI (processor 2) / SI ackn int evt P2
Access level: 3
Can be changed: C(95)
Unit group: -
Min
0
Description:
Select a fail-safe digital input (F-DI) for the signal "acknowledge internal event" (internal fault).
The falling edge at this input resets the status "internal event" in the drive.
The rising edge at this input acknowledges any existing discrepancy errors.
Value:
0:
1:
2:
3:
255:
Dependency:
Refer to: p10006
Note:
The values "static selected" and "static deselected" result in an inactive function of the safe acknowledgment.
F-DI: Fail-safe Digital Input
p10117
SI Motion digital inputs debounce time (processor 2) / SI DI t_debounceP2
Access level: 3
Can be changed: C(95)
Unit group: -
Min
0.00 [ms]
Description:
Sets the debounce time for digital inputs.
The debounce time acts on the following digital inputs:
- Fail-safe digital inputs (F-DI).
- Single-channel digital input 2 (DI 2, read back input for the forced checking procedure).
The debounce time is accepted rounded off to whole milliseconds.
Dependency:
Refer to: p10017
Note:
Example:
Debounce time = 1 ms: Fault pulses of 1 ms are filtered; only pulses longer than 2 ms are processed.
Debounce time = 3 ms: Fault pulses of 3 ms are filtered; only pulses longer than 4 ms are processed.
The debounce result can be read in r10151.
604
Static selected
F-DI 0
F-DI 1
F-DI 2
Static deselected
Calculated: -
Scaling: -
Unit selection: -
Max
2000.00 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
255
Calculated: -
Scaling: -
Unit selection: -
Max
100.00 [ms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 2850, 2851
Factory setting
500.00 [ms]
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
1.00 [ms]
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890