2 Parameters
2.2 List of parameters
r2055[0...2]
PROFIBUS diagnostics standard / PB diag standard
CU250S_V_DP
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Diagnostics display for the PROFIBUS interface.
Index:
[0] = Master bus address
[1] = Master input total length bytes
[2] = Master output total length bytes
r2057
PROFIBUS address switch diagnostics / PB addr_sw diag
CU250S_V_DP
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the setting of the PROFIBUS address switch "DP ADDRESS" on the Control Unit.
Dependency:
Refer to: p0918
Notice:
The display is updated after switching on, and not cyclically.
r2060[0...10]
CO: PROFIdrive PZD receive double word / PZD recv DW
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Connector output to interconnect PZD (setpoints) with double word format received from the fieldbus controller.
Index:
[0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
Dependency:
Refer to: r2050
Notice:
Where there is a multiple interconnection of a connector output, all the connector inputs must either have Integer or
FloatingPoint data types.
A BICO interconnection for a single PZD can only take place either on r2050 or r2060.
p2061[0...15]
CI: PROFIBUS PZD send double word / PZD send DW
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Selects the PZD (actual values) with double word format to be sent to the fieldbus controller.
Index:
[0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
324
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: 4000H
Unit selection: -
Max
-
Calculated: -
Scaling: 4000H
Unit selection: -
Max
-
Data type: Unsigned16
Dyn. index: -
Func. diagram: 2410
Factory setting
-
Data type: Unsigned16
Dyn. index: -
Func. diagram: 2410
Factory setting
-
Data type: Integer32
Dyn. index: -
Func. diagram: 2440, 2468
Factory setting
-
Data type: U32 / Integer32
Dyn. index: -
Func. diagram: 2470
Factory setting
0