Download Print this page

Siemens SINAMICS G120 List Manual page 49

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

p0108[0...n]
Function module 1 / Fct_module 1
Access level: 3
Can be changed: C
Unit group: -
Min
-
Description:
Displays the function modules available on this drive device.
After setting p0010 = 11, additional function modules can be activated – or those that are not required, deactivated. A
change is only active after p0010 = 0.
For this drive device, only index 0 is relevant.
Bit field:
Bit
02
03
04
08
10
13
15
16
17
18
23
25
26
27
28
29
30
31
Dependency:
Active messages can prevent or influence activating a function module.
Refer to: p0010
Refer to: A07089, F13010
Note:
A "function module" is a functional expansion of a drive object that can be activated when commissioning.
p0124[0...n]
CU detection via LED / CU detection LED
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Identification of the Control Unit using an LED.
Note:
While p0124 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Control Unit.
p0133[0...n]
Motor configuration / Motor config
Access level: 2
Can be changed: C(1, 3)
Unit group: -
Min
-
Description:
Configuration of the motor when commissioning the motor.
Bit field:
Bit
00
01
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Signal name
Speed/torque control
Position control
Basic positioner
Extended setpoint channel
Moment of inertia estimator
Safety rotary axis
Encoder
Technology controller
Extended messages/monitoring
Free function blocks
Power Module 230 with STO
Power Module 230
F3E power unit
DC braking
Compound brake
Dynamic brake
Vdc_min controller
Vdc_max controller
Signal name
Motor connection type
Motor 87 Hz operation
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Delta
Yes
2 Parameters
2.2 List of parameters
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
0000 0000 0000 0000 0000 0000 0000
0000 bin
0 signal
Not activated
Not activated
Not activated
Not activated
Not activated
Not activated
Not activated
Not activated
Not activated
Not activated
Not activated
Not activated
Not activated
Not activated
Not activated
Not activated
Not activated
Not activated
Data type: Unsigned8
Dyn. index: PDS
Func. diagram: -
Factory setting
0
Data type: Unsigned16
Dyn. index: MDS
Func. diagram: -
Factory setting
0000 bin
0 signal
Star
No
FP
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
FP
-
-
49

Hide quick links:

Advertisement

loading