Siemens SINAMICS G120 List Manual page 224

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

2 Parameters
2.2 List of parameters
r1242
Vdc_max controller switch-in level / Vdc_max on_level
PM240
Access level: 3
Can be changed: -
Unit group: -
Min
- [V]
Description:
Displays the switch-in level for the Vdc_max controller.
If p1254 = 0 (automatic sensing of the switch-in level = off), then the following applies:
r1242 = 1.15 * sqrt(2) * p0210 (supply voltage)
PM230: r1242 is limited to Vdc_max - 50.0 V.
If p1254 = 1 (automatic sensing of the switch-in level = on), then the following applies:
r1242 = Vdc_max - 50.0 V (Vdc_max: Overvoltage threshold of the power unit)
r1242 = Vdc_max - 25.0 V (for 230 V power units)
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Notice:
If the activation level of the Vdc_max controller is already exceeded in the deactivated state (pulse inhibit) by the DC
link voltage, then the controller can be automatically deactivated (see F07401), so that the drive is not accelerated
the next time that it is activated.
Note:
The Vdc_max controller is not switched back off until the DC link voltage falls below the threshold 0.95 * r1242 and
the controller output is zero.
p1243[0...n]
Vdc_max controller dynamic factor / Vdc_max dyn_factor
PM240
Access level: 3
Can be changed: U, T
Unit group: -
Min
1 [%]
Description:
Sets the dynamic factor for the DC link voltage controller (Vdc_max controller).
100% means that p1250, p1251, and p1252 (gain, integral time, and rate time) are used corresponding to their basic
settings and based on a theoretical controller optimization.
If subsequent optimization is required, this can be carried out using the dynamic factor. In this case p1250, p1251,
p1252 are weighted with the dynamic factor p1243.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
p1245[0...n]
Vdc_min controller switch-in level (kinetic buffering) / Vdc_min on_level
PM240
Access level: 3
Can be changed: U, T
Unit group: -
Min
65 [%]
Description:
Sets the switch-in level for the Vdc-min controller (kinetic buffering).
The value is obtained as follows:
r1246[V] = p1245[%] * sqrt(2) * p0210
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p0210
Warning:
An excessively high value possibly negatively influences normal drive operation, and can mean that after the line
supply returns, the Vdc minimum control can no longer be exited.
224
Calculated: -
Scaling: p2001
Unit selection: -
Max
- [V]
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
10000 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
150 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6220
Factory setting
- [V]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6220
Factory setting
100 [%]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
76 [%]
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890