2 Parameters
2.2 List of parameters
38:
39:
40:
41:
42:
43:
44:
45:
46:
47:
Dependency:
Only the unit of the technology controller parameters are switched over (unit group 9_1).
Refer to: p0596
Note:
When switching over from % into another unit, the following sequence applies:
- set p0596
- set p0595 to the required unit
p0596
Technological unit reference quantity / Tech unit ref qty
CU250S_V (Tech_ctrl)
Access level: 1
CU250S_V_CAN
Can be changed: T
(Tech_ctrl)
Unit group: -
CU250S_V_DP
Min
(Tech_ctrl)
0.01
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the reference quantity for the technological units.
When changing over using changeover parameter p0595 to absolute units, all of the parameters involved refer to the
reference quantity.
Dependency:
Refer to: p0595
Notice:
When changing over from one technological unit into another, or when changing the reference parameter, a
changeover is not made.
p0600[0...n]
Motor temperature sensor for monitoring / Mot temp_sensor
Access level: 2
Can be changed: C(3), U, T
Unit group: -
Min
0
Description:
Sets the sensor to monitor the motor temperature.
The sensor type used is set in p0601.
Value:
0:
1:
11:
12:
Dependency:
Refer to: p0601
Caution:
If, for a selected temperature sensor (p0600 > 0), the motor temperature sensor is not connected but another sensor,
then the temperature adaptation of the motor resistances must be switched out. Otherwise, in controlled-loop
operation, torque errors will occur that will mean that the drive will not be able to be stopped.
Notice:
The parameter is calculated in the drive using p0340 and is inhibited for p0340 > 0.
Note:
For p0600 = 0:
With induction motors, the motor temperature is calculated using the motor temperature model (see also p0612.1).
For p0600 = 1:
Bimetallic switch (p0601 = 4) is not supported.
126
ft³/min
BTU/min
BTU/h
mbar
inch wg
ft wg
m wg
% r.h.
g/kg
ppm
No sensor
Temperature sensor via encoder 1
Temperature sensor via Motor Module / CU terminals
Temperature sensor via CU-D-SUB
Calculated: -
Scaling: -
Unit selection: -
Max
340.28235E36
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
12
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
1.00
Data type: Integer16
Dyn. index: MDS
Func. diagram: 8016
Factory setting
11
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890