Download Print this page

Siemens SINAMICS G120 List Manual page 741

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

Handling BICO technology
Binectors are binary signals that can be freely interconnected (BO = Binector Output).
Binector:
r0723.15
They represent a bit of a "BO:" display parameter (e.g. bit 15 from r0723).
Connectors are "analog signals" that can be freely interconnected (e.g. percentage variables, speeds or torques).
Connector:
r0723
Connectors are also "CO:" display parameters (CO = Connector Output).
Parameterization:
At the signal destination, the required binector or connector is selected using appropriate parameters:
"BI:" parameter for binectors (BI = Binector Input)
or
"CI:" parameter for connectors (CI = Connector Input)
Example:
The main setpoint for the speed controller (CI: p1070) should be received from the output of the motorized potentiometer
(CO: r1050) and the "jog" command (BI: p1055) from Digital Input DI 0 (BO: r0722.0, Terminal 5 (Kl. 5)) on the CU.
Digital Input DI 0
1
r0722.0
Kl. 5
[2220]
Motorized potentiometer
Raise
Lower
[3020]
Parameterizing steps:
1
p1055[0] = 722.0
Terminal 5 (Kl. 5) acts as "Jog bit 0".
p1070[0] = 1050
The output of the motorized potentiometer acts as main setpoint for the speed controller.
2
1
2
Explanations on the function diagrams
Handling BICO technology
Control bit 8
r0967.8
p1055[C]
722.0
[2501]
2
r1050
3
4
Setpoint
channel
Main setpoint
p1070[C]
(1050)
(2050[1])
Jog setpoint 1
[3030]
5
fp_1030_97_61.vsd
05.09.2017
Speed controller
6
7
Function diagram
G120 CU250S-2
V4.7.9
8
- 1030 -

Hide quick links:

Advertisement

loading