Siemens SINAMICS G120 List Manual page 60

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

2 Parameters
2.2 List of parameters
p0295
Fan run-on time / Fan run-on time
Access level: 3
Can be changed: U, T
Unit group: -
Min
0 [s]
Description:
Sets the fan run-on time after the pulses for the power unit have been canceled.
Note:
- Under certain circumstances, the fan can continue to run for longer than was set (e.g. as a result of the excessively
high heat sink temperature).
- For values less than 1 s, a 1 s run on time for the fan is active.
r0296
DC link voltage undervoltage threshold / Vdc U_lower_thresh
Access level: 3
Can be changed: -
Unit group: -
Min
- [V]
Description:
Threshold to detect a DC link undervoltage.
If the DC link voltage falls below this threshold, the drive unit is tripped due to a DC link undervoltage condition.
Dependency:
Refer to: F30003
r0297
DC link voltage overvoltage threshold / Vdc U_upper_thresh
Access level: 3
Can be changed: -
Unit group: -
Min
- [V]
Description:
Threshold to detect a DC link overvoltage.
If the DC link voltage exceeds the threshold specified here, the drive unit is tripped due to DC link overvoltage.
Dependency:
Refer to: F30002
p0300[0...n]
Motor type selection / Mot type sel
PM240
Access level: 2
Can be changed: C(1, 3)
Unit group: -
Min
0
Description:
Selects the motor type or starts to read in the motor parameters for a motor with DRIVE-CLiQ (p0300 = 10000 or
10001, if there is a second data set).
For p0300 < 10000 the following applies:
The first digit of the parameter value always defines the general motor type and corresponds to the third-party motor
belonging to a motor list:
1 = induction motor
2 = synchronous motor
xx = motor without code number
xxx = motor with code number
The type information must be entered to filter motor-specific parameters and to optimize the operating characteristics
and behavior. For example, for synchronous motors, power factor (p0308) is neither used nor displayed (in the
BOP/AOP).
60
Calculated: -
Scaling: -
Unit selection: -
Max
600 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
- [V]
Calculated: -
Scaling: -
Unit selection: -
Max
- [V]
Calculated: -
Scaling: -
Unit selection: -
Max
10001
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
0 [s]
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
- [V]
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8750, 8760, 8850,
8864, 8950, 8964
Factory setting
- [V]
Data type: Integer16
Dyn. index: MDS, p0130
Func. diagram: 6310
Factory setting
0
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890