p2248[0...n]
Technology controller motorized potentiometer ramp-down time /
Tec_ctrMop t_rdown
CU250S_V (Tech_ctrl)
Access level: 2
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: -
CU250S_V_DP
Min
(Tech_ctrl)
0.0 [s]
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency:
Refer to: p2247
Note:
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-down is correspondingly extended.
r2250
CO: Technology controller motorized potentiometer setpoint after RFG /
Tec_ctr mop aftRFG
CU250S_V (Tech_ctrl)
Access level: 2
CU250S_V_CAN
Can be changed: -
(Tech_ctrl)
Unit group: 9_1
CU250S_V_DP
Min
(Tech_ctrl)
- [%]
CU250S_V_PN
(Tech_ctrl)
Description:
Displays the effective setpoint after the internal ramp-function generator for the motorized potentiometer of the
technology controller.
Dependency:
Refer to: r2245
p2251
Technology controller mode / Tec_ctrl mode
CU250S_V (Tech_ctrl)
Access level: 3
CU250S_V_CAN
Can be changed: T
(Tech_ctrl)
Unit group: -
CU250S_V_DP
Min
(Tech_ctrl)
0
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the mode for using the technology controller output.
Value:
0:
1:
Dependency:
p2251 = 0, 1 is only effective if the enable signal of the technology controller is interconnected (p2200 > 0).
p2252
Technology controller configuration / Tec_ctrl config
CU250S_V (Tech_ctrl)
Access level: 3
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: -
CU250S_V_DP
Min
(Tech_ctrl)
-
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the configuration of the technology controller.
Bit field:
Bit
04
05
06
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Technology controller as main speed setpoint
Technology controller as supplementary speed setpoint
Signal name
Ramp-up/ramp-down function generator
bypass
Integrator active for skip speeds
Internal controller limit not displayed
Calculated: -
Scaling: -
Unit selection: -
Max
1000.0 [s]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
-
1 signal
Deactivated
Yes
Yes
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 7954
Factory setting
10.0 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7954
Factory setting
- [%]
Data type: Integer16
Dyn. index: -
Func. diagram: 7958
Factory setting
0
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
0000 0000 bin
0 signal
Activated
No
No
FP
-
-
-
371